A CPU replacement should never be the first time you try to restore a program.

Before the swap

  1. Upload the program from the running CPU and save a copy.
  2. Save the project from your engineering software, with the exact version number.
  3. Record the hardware configuration, addresses and network settings.
  4. Keep any memory card from the old CPU.

After the swap

  1. Download the project to the replacement CPU, or insert the card.
  2. Check the firmware version and network addresses.
  3. Test with the outputs disconnected before returning to production.